VDB

CVE-2018-13799

CVE-2018-13799 PUBLISHED CVSS 9.100000381469727 CRITICAL

A vulnerability has been identified in SIMATIC WinCC OA V3.14 and prior (All versions < V3.14-P021). Improper access control to a data point of the affected product could allow an unauthenticated remote user to escalate its privileges in the context of SIMATIC WinCC OA V3.14. This vulnerability could be exploited by an attacker with network access to port 5678/TCP of the SIMATIC WinCC OA V3.14 server. Successful exploitation requires no user privileges and no user interaction. This vulnerability could allow an attacker to compromise integrity and availability of the SIMATIC WinCC OA system. At the time of advisory publication no public exploitation of this vulnerability was known.

EPSS 0.64% · 71.1th percentile

Risk Scores

CVSS 3.0
9.100000381469727
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H
EPSS Score
0.64%
71.1th percentile

Affected Products

VendorProductVersions
siemenssimatic_wincc_open_architecture0
Siemens AGSIMATIC WinCC OA V3.14 and priorSIMATIC WinCC OA V3.14 and prior : All versions < V3.14-P021

Timeline

  • Sep 11, 2018 CVE Published
  • Apr 14, 2021 EPSS Score
  • Jun 23, 2021 EPSS Score
  • Aug 24, 2021 EPSS Score
  • Oct 26, 2021 EPSS Score
  • Dec 27, 2021 EPSS Score
  • May 2, 2022 EPSS Score
  • Jul 3, 2022 EPSS Score
  • Sep 5, 2022 EPSS Score
  • Nov 6, 2022 EPSS Score
  • Jan 8, 2023 EPSS Score
  • Mar 7, 2023 EPSS Score
Open in Interactive Console →
$ Console Community · 100/wk Open console ›